40 NJR 4915(a)

The New Jersey Board of Public Utilities (Board) is proposing rule changes regarding various aspects of natural gas pipelines (N.J.A.C. 14:7), which address the construction, operation, and maintenance of natural gas transmission and distribution pipelines. These rules explain where pipelines may be constructed, and set requirements for ensuring that the pipelines remain safe both during and after installation. The rules also set specifications that pipeline operators must follow when installing, inspecting, operating and maintaining natural gas pipelines. Some of the changes that should be noted are:

  • Amendments are proposed to clarify that the rules apply to both transmission and distribution lines and that the pipeline operator is the person responsible for compliance.
  • Require that all pipelines constructed in New Jersey in the future meet standards for a Class 4 pipeline location.
  • A reference to the Federal code is added, including the requirements for an integrity management program in 49 CFR 192, Subpart O.
  • Proposed new section provides much more specific and measurable requirements for the number and spacing of valves on distribution lines, and includes factors the operator must consider in determining the appropriate number and spacing of valves. The proposed new section also requires pipeline operators to file an evaluation report with Board staff regarding the number and spacing of valves.
  • Proposed new section N.J.A.C. 14:7-1.11 governs the installation of pipe and its requirements are more stringent than corresponding Federal regulations at 49 CFR 192.325. It requires all gas pipelines to be installed with at least 12 inches separation from any other subsurface structure or facility, whereas the corresponding Federal regulations require 12 inches separation only for the installation of transmission pipelines. It also specifies size and type of wire required for tracer wire on plastic pipe installations. These specifications are more stringent than the corresponding Federal regulations at 49 CFR 192.321, which do not govern the size and type of wire.
  • Proposed new section requires damage prevention efforts consistent with the requirements of Federal regulations at 49 CFR 192.614; requires an operator to take additional measures when the operator becomes aware of potential high risk excavations, such as performing on-site inspection, coordinating with the excavator, continuing surveillance, and checking/verifying clear access to gas valves that may be operated in an emergency. Also, an operator must provide training for operator personnel in preparation for potential high risk excavations around underground gas facilities.

Comments may be submitted through November 1, 2008 by email in Microsoft Word format, or in a format that can be easily converted to Word, to rule.comments@bpu.state.nj.us.

For a copy of the proposed amendments, new rules and repeals, contact Jessica Roger.

Interested in Web-Based Compliance Management Systems?

RCP has the latest technology to help manage all of your permits, inspections, procedures, and data requirements and neatly organize them into one overall compliance assurance system. This includes regulatory tasking, data management, and exception reporting. Because it is web-based, there are no IT issues to struggle through to get started. An institutional memory is created of the compliance history and ongoing compliance requirements, despite operator or personnel turnover. For more information, click here to contact Jessica Roger.